Unsteady Ventilation in a Scaled Room Model with Swirl Ceiling Diffusers

  • Mechanical ventilation of buildings is generally based on steadily operating systems. This field is well known and established. But, an approach based on time-varied supply flow rates might improve indoor air quality, comfort, and energy consumption. Typical time-scales of the variation are in the order of seconds or minutes. Until now, the effects of unsteady ventilation scenarios are not fully described and so, reliable dimensioning rules are missing. Hence, with a better understanding of the flow in unsteady ventilation, systems can be calculated and optimised. To understand the effective mechanisms and derive functional relations between the flow field and variation parameters, full-field optical flow measurements are executed with a particle image velocimetry (PIV) system. Experiments are conducted under isothermal conditions in water in a small-scale room model (1.00 m × 0.67 m × 0.46 m) with two swirl ceiling diffusers, Reynolds-scaling assures similarity. In a series of experiments, the effects of different unsteady ventilation strategies on the flow fields are investigated and compared to steady conditions with the same mean exchange rate. Mean exchange rates, signal types, periods, and amplitudes are varied. Time-averaged normalised velocity fields already indicate notable differences between steady and unsteady cases especially for lower exchange rates: the distribution is more homogeneous in unsteady scenarios compared to steady conditions, and low-velocity areas are reduced while the mean velocity of the room increases. So, unsteady ventilation might be beneficial in terms of improved ventilation and energy savings in partial-load operation. Fast Fourier Transformation (FFT) analyses of the mean velocity for each field over the whole series detect the main frequency of the volume flow variation. By dividing the velocity field into smaller areas, this main frequency is still detected especially in the upper part of the room, but side frequencies play a role in the room as well.
Bitte benutzen Sie diese Referenz, um auf diese Ressource zu verweisen:
https://doi.org/10.25974/fhms-15181

Volltext Dateien herunterladen

Metadaten exportieren

Weitere Dienste

Metadaten
Verfasserangaben:Eva MesenhöllerORCiD, Steffen JacobsORCiD, Peter VennemannORCiD, Jeanette HussongORCiD
URN:urn:nbn:de:hbz:836-opus-151811
URL:https://proceedings.open.tudelft.nl/clima2022/article/view/200
DOI:https://doi.org/10.25974/fhms-15181
DOI der Erstveröffentlichung:https://doi/org/10.34641/clima.2022.200
Titel des übergeordneten Werkes (Englisch):CLIMA 2022 conference
Verlag:TU Delft OPEN
Verlagsort:Delft
Dokumentart:Beitrag in einer Konferenzveröffentlichung
Sprache:Englisch
Datum der Veröffentlichung (online):01.09.2022
Datum der Erstveröffentlichung:16.05.2022
Betreiber des Publikationsservers:FH Münster - University of Applied Sciences
Datum der Freischaltung:01.09.2022
Freies Schlagwort / Tag:PIV; mixing ventilation; room airflow; unsteady ventilation
Fachbereiche:Energie · Gebäude · Umwelt (EGU)
open_access (DINI-Set):open_access
Publikationsliste:Vennemann, Peter
Mesenhöller, Eva
Jacobs, Steffen
Lizenz (Deutsch):License LogoCreative Commons - Namensnennung (CC BY 4.0)